永宏PLC寄存器地址与Modbus寄存器地址对照表
Mapping rule:
Modbus Facon
0xxxx Discrete elements of Ynnn,Xnnn,Mnnnn,Snnn,Tnnn,Cnnn
4xxxx Data Registers of Rnnnn ,Dnnnn,Tnnn,Cnnn
or
00xxxxDiscrete elements of Ynnn,Xnnn,Mnnnn,Snnn,Tnnn,Cnnn
40xxxxData Registers of Rnnnn ,Dnnnn,Tnnn,Cnnn
Available range:
Modbus (5-code) 紫金桥软件中地址FaconDescription
00001----00256 DO 00000----00255 Y0----Y255(Discrete Output)
01001----01256 DO 01000----01255 X0----X255(Discrete Input)
02001----04002 DO 02000----04001 M0----M2001(Discrete M Relay)
06001----07000 DO 06000----06999 S0----S999(Discrete S Relay)
09001----09256 DO 09000----09255T0----T255(Status of T0?T255)
09501----09756 DO 09500----09755 C0----C255(Status of C0?C255)
40001----44168 DO 40000----44167R0----R4167(Holding Register)
45001----45999 DO 45000----45998R5000----R5998(Holding Register or ROR)
46001----48999 DO46000-----48998 D0----D2998(Data Register)
49001----49256 DO49000----49255 T0----T255(Current Value of T0?T255)
49501----49700 DO49500----49699C0----C199 (Current Value of C0?C199,16-bit)
49701----49812 DO49700---49811 C200----C255(Current Value of C200?C255,32-bit)
or
Modbus (6-code) 紫金桥软件中的地址 FaconDescription
000001----000256 DO 00000----00255 Y0----Y255(Discrete Output)
001001----001256 DO 01000----01255 X0----X255(Discrete Input)
002001----004002 DO 02000----04001M0----M2001(Discrete M Relay)
006001----007000 DO 06000----06999S0----S999(Discrete S Relay)
009001----009256 DO 09000----09255T0----T255 (Status of T0?T255)
009501----009756 DO 09500----09755 C0----C255(Status of C0?C255)
400001----404168 HR 00000----04167R0----R4167(Holding Register)
405001----405999 HR 05000----05998R5000----R5998 (Holding Register or ROR)
406001----408999 HR 06000----08998D0----D2998(Data Register)
409001----409256 HR 09000----09255T0----T255(Current Value of T0?T255)
409501----409700 HR09500----09699C0----C199(Current Value of C0?C199,16-bit)
409701----409812 HR9700---9811 C200----C255 (Current Value of C200?C255,32-bit)
※02001----03912 DO 2000---3911M0----M1911(General purpose M Relay)
03913----04002 DO 3912---4001 M1912----M2001(Special M Relay)
40001----43840 DO 4000---43839R0----R3839(General purpose R Register)
43841----43904 DO 43830---43903R3840----R3903(Analog Input Register)
43905----43968 DO 43904---43967R3904----R3967(Analog Output Register)
43969----44168 DO 43969---44167R3968----R4167(Special Register)
FATEK方式 回顶部
紫金桥软件支持通过永宏PLC专有的FATEK协议与永宏PLC通讯。还是按照上面的设置方式,把PLC的通讯方式设置为FATEK通讯方式。进入紫金桥软件开发系统,找到永宏PLC的驱动,双击进入定义设备页,如下图例示,填好设备名,地址,串口号,串口参数,单击完成完成设备定义。